The compact, and elegant design Ceiling Concealed Indoor Unit of the FDMF-Q Series are the perfect answers for the air-conditioners requirements of building with minimum Ceiling Installation space and wide-ranging external static pressure, energy saving efficiency has been improved, thereby reducing electricity consumption.​

Product Category

Available in (kW):

Specification

Ductable Cooling R-32 (FDMF-Q-Series)

r32 icon
Nominal Capacity1.522.533.54
Model NameIDUFDMFQ50AV16FDMFQ71AV16FDMFQ90AV16FDMFQ100AV16FDMFQ125AV16FDMFQ140AV16
ODURZMFQ50AV16RZMFQ71AV16RZMFQ90AV16RZMFQ100AV16RZMFQ125AY16RZMFQ140AY16
PerformanceNominal CapacityTR1.522.533.54
Rated Cooling CapacitykW5.37.1910.512.514
Min ~ Max CapacitykW1.7~5.32.1~7.14.5~95.0~10.55.7~12.56.2~14.0
Rated Power InputkW1.62.352.93.94.55.5
COP-------3.33.023.102.762.782.55
Power supplyV/Hz/ph 230V/50Hz/1ph 400V/50Hz/3ph
Refregerent-------R-32
Indoor UnitCasing Color-------GALVANIZED STEEL COATED
Air Flow Rate (H/M/L)m3/min18/15/12.523/19.5/1632/27/22.540/34/28
CFM635/530/441812/688/5651130/953/7941412/1200/989
Sound Level (H/M/L)dBA35/33/2940/38/3439/34/3242/39/35
External Static PressurePaRATED 50 (50-150)*
Dimensions (HxWxD)mm300x1000x700300x1400x700
Machine Weightkg344345
DrainmmVP25 (I.D. ⌀ 25, O.D. ⌀ 32) 
Remote ControlWireless(Optional)Model No.BRC4M151W16
Receiver KitBRC4M61-6
Wired(Optional)-------BRC1E62/BRC1E63
Outdoor UnitCompressorTypeHermetically Sealed Swing Type
Motor Output kW0.921.21.62.4
RefrigerantkWR-32
Refrigerant Chargekg0.851.041.32.1
Sound LeveldBA Cooling525255
Dimensions (HxWxD)mm595x845x300695x930x350990x940x320
Machine Weightkg31394366
Certified Operation Range°CDB19 to 4819 to 4819 to 4819 to 48  
Piping ConnectionsLiquid (Flare)mm6.356.359.52
Gas (Flare)mm12.715.815.88
Max. Interunit Piping Length m2030
Max. Installation Level Difference m2030
*Initial setting is standard.

Note :

  • Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; Outdoor temp. 35°CDB. Rated heating capacities are based on the following conditions: Indoor temp., 20°CDB; Outdoor temp., 7°CDB, 6°CWB. All unit are being tested and comply to ISO 5151 (Non-ducted unit)